On 1st February 2022, Airedale hosted a panel discussion featuring industry-respected
contributors from both end-user organizations and engineering contractors, to discuss the
burning topic of sustainability with data centers.
Broadcast on the DCD platform, and available to watch here, this article summarises the
discussion. The panel consists of the following people:
Abed Jishi – VP Design, Vantage
Andy Hayes – CTO, Yondr
Dan Loosemore – mediator, DCDDaniel Burczyk – Business Development Manager, Data Centres, Airedale
Jamie Hughes – Head of Technical, Data Centres, Bouygues
Paul Pompili – Divisional Director, ISG
The panel discussion opened with an introductory question looking at what approach to
innovation the data center industry needs to take today, with new challenges ever-presenting
themselves. It was acknowledged that there has been a positive movement towards
sustainability, with a focus on PUE and power usage for increased efficiency.
Sustainability
Adopt sustainability as a mindset, starting with planning and continuing this
mindset through to design
Opening the discussion was Abed Jishi from Vantage, making the point that the starting point is
to adopt sustainability as a mindset, starting with planning and continuing this mindset through to
design and seeing sustainability as a great driver for innovation.
Andy Hayes of Yondr agreed with this point and noted that sustainability is key to the future of
innovation, adding that it is essential to work with clients to understand the future of technology
and technology change. Looking 10-15 years in the future to what the future of IT may look like,
and planning in flexibility to accommodate future IT change is crucial, as well as being mindful of
energy efficiency and sustainability whilst on that journey.
Energy consumption of a data center Daniel Burczyk of Airedale commented on how the data center industry is under the spot lightand
there is more awareness than ever of the energy consumption of a data center, makingeveryone
aware that things need to change and the industry as a collective needs to act.
Daniel explained that at Airedale, the key is to understand the value chain of the data center and
contribute to a point where we can build a more sustainable data center, beyond the product
level. He emphasized the importance of building relationships with everyone in the value chain to
allow us to achieve targets set by both government and ourselves.
Design and build a data center
Jamie Hughes from Bouygues referred to Daniel’s point about early collaboration, not just
around product selection but also right back at the planning stage, highlighting the implication
and importance of the design and build of a data center.
Jamie felt the challenges very much vary depending on the location of the site, mentioning how
geographically the cooling technology can change depending on the ambient environment, and
also the pressures in terms of things like energy resources and control of emissions are also
different and as such there is no silver bullet in terms of the cooling solution.
Finding the right solution
He commented on how the source of the challenges has changed 10 years ago it was
predominantly speed and scale, but now it comes in a different form as pressure from society,
government, and local authorities and this means contractors and end-users should be mindful
of how things are measured, to ensure they are delivering real results.He finished by saying how operators, designers, and builders all play an important part in finding
the right solution for the client and end-user requirements, that meets the pressures of both
societies and themselves to make things cleaner.
Unified approach
Paul Pompili of ISG then took this point of collaboration one step further, observing how clients
are looking for the contractor to take ownership of the design, but unfortunately, the contractor
gets involved in design development far too late and as such opportunities to make greater
efficiencies are missed.
Paul described design teams that work with a silo approach, whereby the architect and structural
engineers work quite closely together, but the M&E consultants have less of a team effort,
looking at the architect to solve and wrap their solutions around them, and Paul put forward the
argument for a more unified approach.
Heat generation
There is a lot of discussion around heat generation within the data center
and the mechanical solution to provide the cooling
He also raised the point that there is a lot of discussion around heat generation within the data
center and the mechanical solution to provide the cooling.
He suggested some of this heat generation could be designed out of the building at a much
earlier stage and commented how he would like to see more innovation; looking at more
intelligent fabrics and looking at the design of the building itself to solve some of the problems
and reduce the amount of energy put into these buildings.Increased Energy Efficiencies
Paul concluded by he would like to see a more unified approach from the start of a project,
utilizing everyone’s knowledge to achieve a better solution. Making the point that chip technology
isn’t improving in terms of efficiency, a different viewpoint is required that focuses on lower
energy solutions.
He acknowledged there might be a trade-off between the space of the development and energy
used in the building to allow for increased energy efficiencies, but that these sorts of things need
to be looked at in the early stages with the developer and the customer and thus it requires
people working as a team instead of individual engineers.
Scalable, reliable, and efficient designs
The conversation then moved on, with Dan raising the issue of how an end-user might evaluate
a site for power, mechanical and electrical requirements, and how would they evaluate
Greenfield projects. Abed noted that whilst most operators strive for scalable, reliable, and
efficient designs, incorporating sustainability early on whilst gaining stakeholder engagement is
essential.
Abed stated that a replicable design is required, this then affords opportunities to be more
efficient. By reducing complexities and bringing in local expertise, sustainability, replicable and
efficiency can be created through the process and design-led thinking allows teams to achieve a
prototype creation that can improve efficiencies.
Sustainable and efficientDan then raised a viewer’s question that had been submitted, asking what the panel felt about
embedded carbon in construction and waste at the design-build phase.
Andy, agreeing with Abed’s earlier point, commented that standardization and continued
evolvement and improvement is a good way to become more sustainable and efficient and said
how Yondr is looking at the full life cycle cost of facilities and request EPDS from suppliers, to
allow them to consider the carbon cost of products.
Improving efficiency
Andy noted that the data center industry can learn about the benefits of standardization from
other industries such as manufacturing, to improve quality and sustainability and ultimately
achieve greater efficiency by being more standardized.
He mentioned the benefits of manufacturing off-site, to reduce the required skill set of labor on
site and improve things like delivery cost and time, and improve sustainability; an area of
discussion he goes more deeply into later on. Andy also supported Paul’s earlier point of getting
the right people involved earlier in the design process, to reap the benefits of that later.
Sustainable data center
Alongside PUE, water use effectiveness and embodied carbon offer
valuable environmental insight
Daniel supported all of the points made and commented on how Airedale maintains a keen eye
on how they can contribute to the sustainable data center. Daniel’s concern is that whilst PUEs
are driving metrics and the industry has experienced improvements over the past 10 years,
these improvements are incremental and the next thing to address is what metrics should and
could be used to assess the data center of today.Alongside PUE, water use effectiveness and embodied carbon offer valuable environmental
insight, and perhaps need to widen the lens to ensure we don’t sacrifice one section of a data
center to another. With solutions getting close to a PUE of 1.0, the question is what does the
sustainable data center of the future look like? And can other technologies use the energy we
are creating?
Tried and tested technologies
Dan then introduced another statement from the viewers’ questions, that data centers demand
revolution rather than evolution and one viewer asked what stands in the way of embracing new
technology, with Dan reflecting on the way mission-critical data centers prefer to adopt tried and
tested technology.
Andy observed that whilst there are emerging technologies in the market such as direct-on-chip,
liquid cooling, or immersion cooling, they are not being adopted at scale and the solution
employed to cool a data center is very much the same as it was 20 years ago, with air passing
through a server, being heated up, going back to a cooling system, being rejected and going
round the cycle again.
Increased efficiency
That said, Andy suggested that a new technological change gives opportunities to do something
different within the space, for example, immersion cooling gives much higher return
temperatures back into the water system which is more useful for the reuse of heat.
He noted that with greater efficiencies, compressors and chillers won’t be required to back things
up, and this is where things can change in time, but at the moment demand at scale is based on
air for a form of cooling.Impact of the SLA
Andy then considered the impact of the SLA and noted that recent times have seen temperature
ranges opening up. He explained that in some instances he has seen temperatures of up to 35
degrees centigrade for periods, whereas they used to be very fixed between 24 to 26 degrees
centigrade, and that drive and change of SLA will help with some of the innovation and help
providers hit sustainability and energy efficiency targets.
Andy explained that everyone in the data center industry works with SLAs and they impact things
like redundancy, temperature, and humidity as well as the way they operate and run the space,
but they all differ. Some companies set their internal SLA, other companies will be setting an
SLA and passing it out to their customers and some have their customers impose an SLA upon
them.
less energy consumption with higher temperatures
Building on this point, Dan asked if less energy consumption with higher temperatures is
possible and what is best practice? Abed responded, stating he has seen a shift from operating
within the ASHRAE recommended envelope to the allowable range. He has seen supply
temperatures increase from 27 degrees centigrade to almost 30 degrees centigrade, but said it
was important to recognize that what an operator can control is quite limited.
End users are driven by the availability of equipment which is limited by temperatures and it is a
cycle. He noted how Vantage has built facilities that can withstand 100% or even 110% of the
load dictated by customers, but the ramp-up to withstand the 100% sometimes takes a few years
so agility is important in operations and it is critical to work smart.
simple, cost-effective mechanismThat agility of operations and being smart and efficient lead to more
sustainable data center environments
Abed again emphasized the point that having sustainability as a mindset, through design,
operation, and construction, means some things can be controlled and improvements that can
be incorporated within the white space. Abed gave the example of hot and cold aisle
containment, describing it as a simple, cost-effective mechanism that has a significant impact.
He then added that other technologies like sensors, AI, and software can be employed to read
how the heat load is being distributed and to apply the right amount of cooling where it is needed
the most. All these initiatives support the view that agility of operations and being smart and
efficient lead to more sustainable data center environments.
Adopting new technology
Daniel noted again the developments of the past few years about rising temperatures and the
need to get to a point where the envelope can be opened up beyond incremental changes, but
this would require new technologies, which would need to be proven before being rolled out into
a 1MW facility.
He commented on how expansions over the past 3 years have been fast and the message he
gets is not that the data center provider is chasing the latest technology, but instead demands
speed of build; Daniel believes a more sustainable data center has to develop alongside market
growth itself. Adopting technology and with more companies opening up the envelope which we
give recommendations is leading to change. It may be happening slowly, but it is happening.
selection criteria and prioritize solutions
The next question Dan proposed was how does increased demand impact selection criteria and
how do end-users prioritize solutions? Abed was very clear that customers seek confidence inthe design and for that to happen, Abed has to have confidence in his equipment.
He said one of the drivers for sustainability is having something that can be replicated, and as
such, it is important to have confidence in the performance of equipment in different climates and
locations, to deliver different capacities. Confidence and performance are in his view key to the
selection process.
Flexible technology
Andy seconded this view, stating his customers also demand global consistency, which in itself
leads to standardization., He noted that a facility’s life cycle could be up to 20 years, whereas IT
refresh can be 3 or 4 years, and as such, there is an imbalance, which they address by building
flexibility into their design.
He acknowledged that new technologies like immersion cooling are being explored, but is
uncertain as to whether they will ever be deployed at the hyperscale level, noting it will very
much depend on how reliable they are in comparison to the current way of working. He finished
by stating the future is probably a very different technology altogether, but we are a while off
from that and so for now, having the flexibility to adopt new emerging technology over the next
10 to 15 years is key.
consistent air-cooled standardized IT model
Jamie concurred with Andy, that there is a consistent air-cooled standardized IT model in
operation at the moment, which may vary within the detail, but is ultimately the same cooling
solution.
Jamie said he has experienced developments with end-users giving very clear detailed
requirements about how they will deploy the initial step of IT and this brings opportunities for
optimization of the facility, stating that it is possible to have a standard model with the ability tooptimize the solution to drive energy efficiency. Jamie noted that end-users are giving the
information much earlier.
a shift from R410A to R32
With regards to selection criteria from a sustainability point, Jamie felt there is more than energy
to be considered and commented how the changing use of refrigerants may have been driven by
EU regulations, but has continued citing the shift from R410A to R32.
Jamie stated there is a real tangible benefit from this step change, that wouldn’t be reflected in
PUE. He also added that step changes around embodied carbon are happening and are
promising.
efficiency solutions
One of the challenges from client teams is that they want to restrict the data
center facility to smaller spaces
The final question raised by Dan was that of circularity with the data center industry, stating that
PUEs don’t encapsulate everything and if the limit of ambition is to heat the sea more slowly then
perhaps they haven’t done enough?
Paul opened the discussion around this point, noting that ISG is keen on heat reuse, but one of
the challenges seen from client teams is that they understandably want to maximize their real
estate and so restrict the data center facility to smaller spaces, which then restricts the
engineering efficiency solutions opportunities.
environmental benefits
Paul felt that if the data center could be associated with horticultural environments andresidential facilities, then perhaps a better method of reusing the heat could be developed,
especially in the horticultural sector which could use it year-round and would be beneficial to the
local environment and local population as well.
However, he noted there are limitations due to the density of the buildings in city locations. He
cited facilities over 100MW in say a central London location, stating that if the capacity could be
reduced to 40 or 50MW, then there would be more space that could be utilized for more
environmental benefits.
Reuse energy effectively
Paul believes contractors need to start challenging the mega users of hyperscale data centers,
reminding them of their environmental responsibility and encouraging those in the commercial
sector to reuse their energy effectively, as he has seen in some public-funded projects.
Paul gave an example of a project he worked on in 2008, which was a large data center for a
government body. It was extremely large and less efficient in terms of its square meterage in
today’s terms, but it was very low energy with PUE 1.1, all free cooling, and no chillers involved;
it continues to provide a high-density cooling facility for the government today.
Benefit of data
Paul noted that some of the biggest organizations in the world are making lots of revenue from
using these data centers, but the benefits need to reach the environment and local population as
well the shareholders.
Andy stated the data center does need to be more useful and consider its impact is on the local
community and environment. He explained a data center with a standard air cooling solution
kicks back 35 to 40 degrees centigrade water and he questioned how useful is that into legacy or
existing heating systems, however, it could work with new build residential opportunities where anew district heating system could be designed to work with.
opportunities from hyperscale data centers
That said, he explained that some district heating systems are tied into power stations, and a
data center couldn’t improve on what that can offer. He explained that things like swimming
pools and greenhouses offer opportunities, but cloud computing facilities are typically built in
urban areas where there is little call for such things.
He felt the most opportunities come from larger hyperscale data centers in big out-of-town
facilities and he has seen examples of such work being done, along with examples of seawater
cooling, but it is very much location dependent.
impact of a data center project
A further point Andy made, which isn’t location-dependent, is the impact a data center project
can have on a local community.
He explained that the development of a large scale data center may bring 1,000 or even 2,000
people into an area and this helps them for the construction phase of maybe 2 to 3 years, but
then they pull out, leaving just 20 or 30 highly skilled people who have been brought in from
outside the area, thus the project having a very obvious positive, then negative impact.
Improving the community
By considering the overall lifecycle of the data center, the focus shifts to how to positively impact
the area. Going back to Andy’s earlier point of having lower-skilled people on-site during
construction, he explained that by delivering part-constructed elements, it is possible to train
people in the local area so they can build the center.Further to this, embedding technology in the operation of the site such as AR and VR means
less skilled people can work in the operating environment. These people can be trained within a
few months, eliminating the need for lengthy experience and formal qualifications, and these
people will stay and improve the community.
collaborative approach
Abed finished by confirming all Vantage DC are heat reuse ready, but they
need the systems to connect to
Abed was keen to clear up a misconception that the data center industry is resisting supplying
heat to its community, explaining that the investment required for any data center to have a
facility for heat reuse is very minimal. The issue usually is the infrastructure required to take the
waste heat away and the councils or local authorities don’t necessarily have the funding for it.
Abed suggested a collaborative approach between local councils and communities to
demonstrate how both entities can benefit from the infrastructure might be a solution. Abed
finished by confirming all Vantage DC are heat reuse ready, as are many other providers, but
they need the systems to connect to.
Integration between data center
Daniel closed the discussion, observing that the conversations around collaboration within and
beyond the data center industry can lead the way to improved efficiencies with the facilities,
noting that further sharing of information and increased integration between data center
providers and local authorities could lead to more environmental advancements within the
community as a whole.
He recognized some progress, in that the conversation looking at how to do this is at leasthappening now.
The efficiency of Airedale products
Daniel mentioned the intense focus on efficiency delivered by Airedale and how this is afforded
by its specialist engineers and state-of-the-art research and development facilities at its UK HQ.
He concluded that Airedale products facilitate the current market, making the required
incremental changes but eventually we need to be ready to integrate the data center into the
community and be ready for what that might look like.